@taddydigest: Why does the air conditioner breaker keep tripping? Check out my youtube channel for more videos... #breakertrip #airconditioner #airconditioning #airconditionerrepair #taddydigest #DIY #education #electrician #hvac #circuitbreaker #electrical #thermalimaging #hvactraining #hvactechnician #hvaclife #hvacwork #hvacguy #hvacvideos

Taddy Digest
Taddy Digest
Open In TikTok:
Region: US
Tuesday 09 July 2024 11:46:54 GMT
301477
7365
427
395

Music

Download

Comments

sparkyjoel72
sparkyjoel72 :
8awg on a 60 amp breaker would have been the correct install.
2024-07-09 21:11:21
13
c.m.h88
CH :
Wire only needs to be sufficient for the minimum circuit amps. Wire to the minimum, breaker to the max. You'll end up with 8 gauge wire on a 60 and that's totally fine.
2024-07-09 16:41:12
7
thollingsworth997
T Hollingsworth997 :
that breaker be trippin
2024-07-19 09:17:16
0
br4nd0n444
Brandon Harris :
so min circuit says 34 amps then max circuit says 60 amp 50 amp installed. yet HVAC guy thinks a 50 amp is no good for that installation... a 40 amp / 50 amp / 60 amp all okay to use.
2024-07-10 01:35:16
17
dirkbrant1
dirkbrant1 :
shouldn't be a breaker outside, should only be a disconnect
2024-07-09 21:31:11
5
don_w_mi
Don W :
60 amp is "max" but the 50 amp is adequate and sufficient.
2024-07-18 14:29:18
16
nathanokken
Nathan okken :
Way better than the other ac service technical videos 😂💀
2024-07-09 12:11:56
76
kissitslowly
nunya3000 :
just curious the maximum ocpd is 60, doesn't mean it needs a 60 Amp ocpd
2024-07-09 14:07:27
11
scottiesq
scottiesq :
Capacitor. If it’s not the capacitor, replace the entire system, including the ductwork. You also need to install a hepa filter and a UV light.
2024-07-09 16:22:31
2
hikeeba
hikeeba :
I just started an electrical maintenance job after doing machine building for 5 years and I use a thermo scanner on the panels behind start digging around, a lot it machines don’t have schematics…
2024-07-20 06:24:13
0
electriciannamedtyler
ElectricianNamedTyler :
The wire does absolutely not have to be sized to the breaker! Just the minimum ampacity. Which is 34.7=8awg.
2024-07-09 18:33:50
0
msshields51
Bull Shit Fisherman :
What is start up amps
2024-07-09 12:27:25
0
trulynicky
ωуαиι¢ку🎸 :
Then what’s the point of having one outside breaker and one inside and the one outside has the chance of overheating
2024-07-16 22:59:48
1
luismanuel.el.rey
Luismanuel el Rey :
always learning......from San diego california Daikin Goodman Amana rep
2024-07-09 18:21:45
0
ukcatsrock1
Jeff Campbell :
Well done good detective work
2024-07-09 15:25:01
39
tim_wojo03
Tim Wojo 03 :
Amp it on both sides of breaker
2024-07-09 19:49:57
10
stevemeeks0
Steve Meeks :
That’s great information
2024-07-09 12:55:03
13
specopstoon
specopstoon :
minimum circuit ampacity is for the ampacity or capacity of the wire / wire size. RLA (running load amperage) is the max the unit should be running at.
2024-07-29 09:00:34
6
edwardlesk
Eddie 🐐 :
thank you tad - we all say in unison
2024-07-09 12:43:32
8
rocko8437
Rock :
6 wire is only good for 50 amps unless it’s thhn
2024-07-10 00:02:21
2
stuartyoung68
Stuart Young :
First, let the system run for 10 minutes. If the breaker becomes extremely warm (100-120 degrees) replace it.
2024-07-09 18:01:53
4
richmontemayor
rich montemayor :
Great job sir👍👍👍 helpful video
2024-07-18 15:42:31
1